“FK” Cable junction boxes for approved intrinsic fire resistance and insulation integrity
- Intrinsic fire resistance following DIN 4102 Part 12 (German standard) in combination with function-retaining cables
- Insulation integrity PH120 following BS EN 50200 in combination with insulation retaining cables
- Screw anchors, high-temperature-resistant ceramic terminal E30 up to E90, and cable entries are included as standard
- Multi-level knockouts for cable glands in different sizes
- Closes quickly by a quarter turn – locked position well visible (open – locked)
- Material: PC-GFS polycarbonate
- Colour: orange, RAL 2003
- Glow wire test in accordance with IEC 60695-2-11: 960 °C, flame-retardant, self-extinguishing
- Resistance to impact: IK 09 (10 Joule)
- Degree of protection: IP 65/66
Cable entry via integrated elastic membranes
Alternatively, a cable gland can be set after removing the elastic membrane and extension ring
Cable entry through the bottom of the box via integrated elastic membrane
Retaining strap prevents the lid from falling or losing
Closes quickly by a quarter turn – closed position is visible
Multi-level knockouts for cable glands in different sizes
Cable entry also possible from the rear side
Burning behaviour in glow wire test 750 °C / 960 °C
High impact withstand IK 09 (10 joule)
All terminals with 2 clamping units per pole
Terminals prevent damage of conductors, also for flexible conductors without ferrule
Various conductor cross sections and conductor types
High-position terminals with more space for wiring
Different terminal positions and fastening options
External brackets for fastening are always included