If required, a ventilation hole can be made in the cover, reducing the protection type from IP67 to IP30.

If an outer contact (20) should weld, then the forced operated inner contact (12) driven by the actuator remains open. The rotating armature remains free to move. The unaffected contact pairs can operate normally, (i. e. their function to make or break remains unaffected).

Nominal input voltage: 230 V AC/DC; 2,50 mm²; gray

If an inner contact should weld (12) then the movement of the rotating armature is blocked via the operator. Open contacts of all four contact pairs remain open. This arrangement corresponds to conventional, force-guided operation.

Category: Tags: , ,

Technical data

Control Circuit

Nominal input voltage UN AC/DC 230 V
Input voltage range -15 … +20 %
Nominal input current at UN 14 mA

Load circuit

Number of break/switch-off contacts 4
Number of make/switch-on contacts 4
Contact material (relay) AgSnO2
Limiting continuous current 6 A
Switching voltage (max.) AC 250 V
Switching power (resistive) max. AC 1500 VA
Recommended minimum load 10 V / 10 mA
Pull-in time (typ.) 18ms
Drop-out time (typ.) 21ms
Bounce time (typ.) 4ms
Electrical life (NO; resistive load; 23 °C) 100 x 10³ switching operations
Mechanical life 10 x 10⁶ switching operations
Mechanical force-guided operation Type B

Safety and protection

Rated voltage 250V
Type of circuits Secondary circuits
Note on insulation parameters per EN 61010-1
Overvoltage category II
Pollution degree 2
Dielectric strength (control/load circuit) (AC, 1 min) 2.5 kVrms
Dielectric strength (open contact) (AC, 1 min) 1.3 kVrms
Dielectric strength (load/load circuit) (AC, 1 min) 2.5 kVrms
Insulation type (control/load circuit) Basic insulation
Insulation type (open contact) Functional insulation
Insulation type (load/load circuit) Basic insulation
Insulation type (adjacent devices) Reinforced insulation (safe isolation)

Connection data

Connection technology CAGE CLAMP®
WAGO connector WAGO 256 Series
Solid conductor 0.08 … 2.5 mm² / 28 … 12 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 12 AWG
Strip length 5 … 6 mm / 0.2 … 0.24 inches

Physical data

Width 63.5 mm / 2.5 inches
Height 85 mm / 3.346 inches
Depth 40 mm / 1.575 inches

Mechanical data

Installation DIN-35 rail

Material Data

Color gray
Fire load 1.131MJ
Weight 113.3g

Environmental requirements

Ambient temperature (operation at UN) -40 … +70 °C
Ambient temperature (storage) -40 … +80 °C
Processing temperature -25 … +50 °C
Temperature range of connection cable ≥ (Tambient + 20 K)
Relative humidity 5 … 85 %
Operating altitude (max.) 2000m

Standards and specifications

Standards/specifications EN 60664-1
EN 50205
EN 61810-1
ESTI (SEV): 09.1133
UL 508: E120782
TÜV: 968/EZ 116.02/09

Commercial data

Product Group 6 (INTERFACE ELECTRONIC)
eCl@ss 10.0 27-37-16-01
eCl@ss 10.0 27-37-16-01
ETIM 8.0 EC001437
ETIM 8.0 EC001437
PU (SPU) 1 pcs
Packaging type box
Country of origin DE
GTIN 4017332160209
Customs tariff number 85364900990

Environmental Product Compliance

CAS-No. 7439-92-1
79-94-7
REACH Candidate List Substance 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol
Lead
RoHS Compliance Status Compliant,With Exemption
RoHS Exemption 6(c)
7(a)
7(c)-I
7(c)-II

Additional information